Cable trunking systems and cable ducting systems for electrical installations - Part 2-2: Particular requirements - Cable trunking systems and cable ducting systems intended for mounting underfloor, flushfloor, or onfloor (IEC 61084-2-2:2017)

This part 2-2 of the EN IEC 61084 series specifies particular requirements and tests for cable trunking systems (CTS) and cable ducting systems (CDS) intended for mounting underfloor, flushfloor or onfloor.

Elektroinstallationskanalsysteme für elektrische Installationen - Teil 2-2: Besondere Anforderungen für Elektroinstallationskanalsysteme für die Montage unterboden, bodenbündig, oder aufboden (IEC 61084-2-2:2017)

Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques - Partie 2-2: Exigences particulières - Systèmes de goulottes et systèmes de conduits-profilés prévus pour être montés en sous-sol, encastrés dans le sol, ou sur le sol (IEC 61084-2-2:2017)

IEC 61084-2-2:2017 spécifie les exigences et les essais pour les systèmes de goulottes (SG) et les systèmes de conduits-profilés (SCP) destinés au logement de conducteurs isolés, câbles et éventuels autres équipements électriques et, si nécessaire, à leur séparation de protection électrique, dans des installations électriques et/ou de systèmes de communication. La tension maximale de ces installations est de 1 000 V en courant alternatif et 1 500 V en courant continu.
Ces systèmes sont destinés à être montés sous le sol, encastrés dans le sol, ou sur le sol.
Le présent document ne s’applique pas aux SG/SCP prévus pour être fixés à un mur et soutenus par le sol.
Le présent document ne s’applique pas aux systèmes de conduits, systèmes de chemins de câble, systèmes d’échelles à câble, systèmes de canalisations préfabriquées ou aux équipements couverts par d’autres normes.
Cette deuxième édition annule et remplace la première édition parue en 2003. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
- classification;
- construction;
- propriétés mécaniques et électriques.
Cette Norme internationale doit être utilisée conjointement avec l’IEC 61084-1:2017.

Sistemi kabelskih korit in sistemi kabelskih cevi za električne inštalacije - 2-2. del: Posebne zahteve - Sistemi kabelskih korit in sistemi kabelskih cevi, namenjenih za montažo pod tlemi, po golih tleh ali po tleh (IEC 61084-2-2:2017)

Ta 2-2. del skupine standardov EN IEC 61084 določa posebne zahteve in preskuse za sisteme kabelskih korit (CTS) in sisteme kabelskih cevi (CDS), namenjene za montažo pod tlemi, po golih tleh ali po tleh.

General Information

Status
Published
Public Enquiry End Date
28-Feb-2023
Publication Date
22-Sep-2024
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
18-Sep-2024
Due Date
23-Nov-2024
Completion Date
23-Sep-2024

Relations

Standard
SIST EN IEC 61084-2-2:2024 - BARVE
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2024
Sistemi kabelskih korit in sistemi kabelskih cevi za električne inštalacije - 2-2. del:
Posebne zahteve - Sistemi kabelskih korit in sistemi kabelskih cevi, namenjenih za
montažo pod tlemi, po golih tleh ali po tleh (IEC 61084-2-2:2017)
Cable trunking systems and cable ducting systems for electrical installations - Part 2-2:
Particular requirements - Cable trunking systems and cable ducting systems intended for
mounting underfloor, flushfloor, or onfloor (IEC 61084-2-2:2017)
Elektroinstallationskanalsysteme für elektrische Installationen - Teil 2-2: Besondere
Anforderungen für Elektroinstallationskanalsysteme für die Montage unterboden,
bodenbündig, oder aufboden (IEC 61084-2-2:2017)
Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques -
Partie 2-2: Exigences particulières - Systèmes de goulottes et systèmes de conduits-
profilés prévus pour être montés en sous-sol, encastrés dans le sol, ou sur le sol (IEC
61084-2-2:2017)
Ta slovenski standard je istoveten z: EN IEC 61084-2-2:2024
ICS:
29.120.10 Inštalacijske cevi za Conduits for electrical
električne namene purposes
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61084-2-2

NORME EUROPÉENNE
EUROPÄISCHE NORM September 2024
ICS 29.060.01; 29.120.10 Supersedes EN 50085-2-2:2008
English Version
Cable trunking systems and cable ducting systems for electrical
installations - Part 2-2: Particular requirements - Cable trunking
systems and cable ducting systems intended for mounting
underfloor, flushfloor, or onfloor
(IEC 61084-2-2:2017)
Systèmes de goulottes et systèmes de conduits-profilés Installationskanalsysteme für elektrische Installationen - Teil
pour installations électriques - Partie 2-2: Exigences 2-2: Besondere Anforderungen - Installationskanalsysteme
particulières - Systèmes de goulottes et systèmes de für die Montage unterflur, bodenbündig oder aufflur
conduits-profilés prévus pour être montés en sous-sol, (IEC 61084-2-2:2017)
encastrés dans le sol, ou sur le sol
(IEC 61084-2-2:2017)
This European Standard was approved by CENELEC on 2024-08-05. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61084-2-2:2024 E

European foreword
This document (EN IEC 61084-2-2:2024) consists of the text of document IEC 61084-2-2:2017,
prepared by SC 23A "Cable management systems" of IEC/TC 23 "Electrical accessories".
The following dates are fixed:
• latest date by which this document has to be (dop) 2025-08-05
implemented at national level by publication of an
identical national standard or by endorsement
• latest date by which the national standards (dow) 2029-08-05
conflicting with this document have to be withdrawn
This document supersedes EN 50085-2-2:2008 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a standardization request addressed to CENELEC by the
European Commission. The Standing Committee of the EFTA States subsequently approves these
requests for its Member States.
For the relationship with EU Legislation, see informative Annex ZZ, which is an integral part of
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 61084-2-2:2017 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated:
IEC 61084-2-4:2017 NOTE Approved as EN IEC 61084-2-4:2024 (not modified)

IEC 61084-2-2 ®
Edition 2.0 2017-03
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Cable trunking systems and cable ducting systems for electrical installations –

Part 2-2: Particular requirements – Cable trunking systems and cable ducting

systems intended for mounting underfloor, flushfloor, or onfloor

Systèmes de goulottes et systèmes de conduits-profilés pour installations

électriques –
Partie 2-2: Exigences particulières – Systèmes de goulottes et systèmes de

conduits-profilés prévus pour être montés en sous-sol, encastrés dans le sol,

ou sur le sol
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.060.01; 29.120.10 ISBN 978-2-8322-4119-6

– 2 – IEC 61084-2-2:2017 © IEC 2017
CONTENTS
FOREWORD . 3
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 General requirements . 6
5 General conditions for tests . 7
6 Classification . 7
7 Marking and documentation . 7
8 Dimensions. 8
9 Construction . 8
10 Mechanical properties. 9
11 Electrical properties . 14
12 Thermal properties . 14
13 Fire hazard . 14
14 External influences . 14
15 Electromagnetic compatibility . 15
Annex A (informative) Types of cable trunking systems (CTS) and cable ducting
systems (CDS) . 27
Annex B (normative) CTS/CDS IK code . 28
Annex AA (normative) Mechanical load tests . 29
Bibliography . 31

Figure 101 – Types and application of CTS/CDS for underfloor, flushfloor or onfloor
installations . 16
Figure 102 – Examples of trunking and ducting installations . 17
Figure 103 – Example of underfloor embedded CDS according to 3.101 . 18
Figure 104 – Example of flushfloor CTS according to 3.102 . 19
Figure 105 – Example of onfloor CTS according to 3.103 . 20
Figure 106 – Principles for arrangement . 21
Figure 107 – Examples for arrangement . 22
Figure 108 – Load test set-up for CTS/CDS in accordance with 10.5.103 . 24
Figure 109 – Load test set-up for CTS/CDS in accordance with 10.5.104 . 26

Table A.2 – Types of CTS and CDS for floor installation . 27
Table AA.1 – Mechanical load tests . 29

IEC 61084-2-2:2017 © IEC 2017 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
CABLE TRUNKING SYSTEMS AND CABLE DUCTING
SYSTEMS FOR ELECTRICAL INSTALLATIONS –

Part 2-2: Particular requirements – Cable trunking systems and cable
ducting systems intended for mounting underfloor, flushfloor, or onfloor

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61084-2-2 has been prepared by subcommittee 23A: Cable
management systems, of IEC technical committee 23: Electrical accessories.
This second edition cancels and replaces the first edition published in 2003. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
• classification;
• construction;
• mechanical and electrical properties.
This International standard is to be used in conjunction with IEC 61084-1:2017.

– 4 – IEC 61084-2-2:2017 © IEC 2017
The text of this standard is based on the following documents:
FDIS Report on voting
23A/828/FDIS 23A/836/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This part of the IEC 61084 series supplements or modifies the corresponding clauses of
IEC 61084-1:2017 as follows:
– where no particular clause or subclause of IEC 61084-1 is mentioned, the corresponding
clause or subclause of IEC 61084-1 applies as far as it is reasonable;
– where “addition” or “replacement” is stated, the relevant text of IEC 61084-1 is to be
adapted accordingly;
– subclauses, figures and tables which are additional to those in IEC 61084-1 are numbered
starting from 101.
In this standard, the following print types are used:
– requirements and definitions: roman type;
– compliance statements: italic type.
A list of all parts in the IEC 61084 series, published under the general title Cable trunking and
cable ducting systems for electrical installations, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC website under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
IEC 61084-2-2:2017 © IEC 2017 – 5 –
CABLE TRUNKING SYSTEMS AND CABLE DUCTING
SYSTEMS FOR ELECTRICAL INSTALLATIONS –

Part 2-2: Particular requirements – Cable trunking systems and cable
ducting systems intended for mounting underfloor, flushfloor, or onfloor

1 Scope
This part of the IEC 61084 series specifies requirements and tests for cable trunking systems
(CTS) and cable ducting systems (CDS) intended for the accommodation, and where
necessary for the electrically protective separation, of insulated conductors, cables and
possibly other electrical equipment in electrical and/or communication systems installations.
The maximum voltage of these installations is 1 000 V AC and 1 500 V DC.
These systems are intended for mounting underfloor, flushfloor or onfloor.
This document does not apply to CTS/CDS which are intended to be fixed to the wall and
supported by the floor.
This document does not apply to conduit systems, cable tray systems, cable ladder systems,
power track systems or equipment covered by other standards.
2 Normative references
This clause of Part 1 is applicable, except as follows:
Addition:
IEC 60068-2-60:2015, Environmental testing – Part 2-60: Tests – Test Ke: Flowing mixed gas
corrosion test
IEC 60068-2-75:2014, Environmental testing – Part 2-75: Tests – Test Eh: Hammer tests
IEC 61084-1:2017, Cable trunking systems and cable ducting systems for electrical
installations – Part 1: General requirements
3 Terms and definitions
This clause of Part 1 is applicable, except as follows:
3.1 Replace Note 1 to entry by:
Note 1 to entry: Different types of CTS are shown in Figure 101 and explained in Annex A.
3.2 Replace Note 1 to entry by:
Note 1 to entry: Different types of CDS are shown in Figure 101 and explained in Annex A.

– 6 – IEC 61084-2-2:2017 © IEC 2017
3.3 Addition:
f) service unit
Replace Note 1 to entry by:
Note 1 to entry: A system does not necessarily include all system components a) to f). Different combinations of
system components can be used.
Addition:
3.101
underfloor CTS/CDS
CTS/CDS whose components, except access units and service units, are intended to be
mounted within or under a floor and in normal use are not exposed to traffic loads
Note 1 to entry: See Figures 102a), 102c) and 103.
3.102
flushfloor CTS/CDS
CTS/CDS whose components, except access units and service units, are intended to be
mounted flush such that the height above the upper level of the floor covering is not more
than 4 mm
Note 1 to entry: The upper surface is considered to be exposed to traffic loads.
Note 1 to entry: See Figures 102b) and 104.
3.103
onfloor CTS/CDS
CTS/CDS whose components are intended to be mounted on a floor such that the height
above the upper level of the floor covering is greater than 4 mm
Note 1 to entry: The upper surface is considered to be exposed to traffic loads.
Note 2 to entry: See Figures 102d) and 105.
3.104
access unit
system component intended to provide access to insulated conductors or cables
3.105
service unit
system component intended for incorporation of one or more apparatus either directly or by
means of one or more apparatus mounting devices
3.106
service unit
service unit which has no cables connected to electrical equipment
3.107
service unit
service unit which has cables connected to electrical equipment
4 General requirements
This clause of Part 1 is applicable.

IEC 61084-2-2:2017 © IEC 2017 – 7 –
5 General conditions for tests
This clause of Part 1 is applicable.
6 Classification
This clause of Part 1 is applicable, except as follows:
Additional subclauses:
6.101 According to floor treatment
6.101.1 CTS/CDS for dry-treatment of floor
6.101.2 CTS/CDS for wet-treatment of floor when the service unit is not in use
6.101.3 CTS/CDS for wet-treatment of floor when the service unit is in use
6.102 According to resistance to vertical load applied through small surface area
6.102.1 CTS/CDS for 500 N
6.102.2 CTS/CDS for 750 N
6.102.3 CTS/CDS for 1 000 N
6.102.4 CTS/CDS for 1 500 N
6.102.5 CTS/CDS for 2 000 N
6.102.6 CTS/CDS for 2 500 N
6.102.7 CTS/CDS for 3 000 N
6.103 Optional classification according to resistance to vertical load applied through
large surface area
6.103.1 CTS/CDS for 2 000 N
6.103.2 CTS/CDS for 3 000 N
6.103.3 CTS/CDS for 5 000 N
6.103.4 CTS/CDS for 10 000 N
6.103.5 CTS/CDS for 15 000 N
7 Marking and documentation
This clause of Part 1 is applicable, except as follows:
Additional subclauses:
7.101 Access units and service units of systems classified according to 6.101.1 shall be
marked that they are suitable for dry treatment of floor only. The marking shall be visible by
the user which may be achieved by opening the cover.
NOTE This marking can be in the form of text or graphic.

– 8 – IEC 61084-2-2:2017 © IEC 2017
7.102 Service units shall be marked with a warning about the potential damage to electrical
accessories by closing the cover. The marking shall be visible by the user which may be
achieved by opening the cover.
NOTE This marking can be in the form of text or graphic.
7.103 Compliance with 7.101 and 7.102 is checked by inspection.
8 Dimensions
This clause of Part 1 is applicable, except as follows:
Addition:
There are no dimensions requirements.
9 Construction
This clause of Part 1 is applicable, except as follows:
Addition:
9.101 Access covers of underfloor, flushfloor and onfloor CTS/CDS, which in normal use are
subjected to external mechanical loads, shall resist movement and unintentional opening.
Compliance is checked by inspection and by the tests of 10.5.
9.102 Service units installed flushfloor shall protect the installed electrical apparatus and the
plug from direct impact when in use. This protection shall be effective and shall not cause
damage to the outgoing cable.
Compliance is checked by inspection and by the tests of 10.3.
9.103 It shall be possible to securely fix:
– service units to the system;
– electrical apparatus to the service units.
Compliance is checked by the tests of 10.3 and 10.5.1.
9.104 When the service unit is not in use, it shall be possible to close openings intended for
the passage of cables.
Openings, when in use, in underfloor and flushfloor CTS/CDS, for the passage of cables,
need not be closed if one of its dimensions is less than 20 mm in one direction.
Compliance is checked by inspection and measurement.
9.105 Underfloor and flushfloor CTS/CDS which in normal use are embedded in screed
material shall be protected against ingress of the screed material.
Openings leading to the interior of underfloor and flushfloor CTS/CDS which in normal use,
are located below the upper level of the floor without covering, shall not be wider than 7 mm
in one direction.
IEC 61084-2-2:2017 © IEC 2017 – 9 –
Compliance is checked by inspection and measurement.
NOTE The dimensioning of the maximum width of the clear opening is based on the grain size of cementitious
screeds.
9.106 CTS/CDS declared according to 6.101.2 and 6.101.3 shall avoid water coming into
contact with insulated conductors and live parts during wet-treatment of floor by one or a
combination of the following methods which may vary within the system:
– method 1: ensuring by design that water does not come into contact with insulated
conductors and live parts when the water level is 10 mm above the upper level of the floor
covering;
– method 2: providing an IP rating not less than IPX4;
– method 3: providing manufacturer's instructions which require that insulated conductors
and live parts are positioned not less than 10 mm above the upper level of the floor
covering.
For method 1, compliance is checked by measurement. For method 2, compliance is checked
by the test of 14.1.2. For method 3, compliance is checked by inspection.
9.107 Access cover of service unit, if any, shall withstand repeated opening and closing as
in normal use.
Compliance is checked by 100 cycles of opening and closing of the access cover.
After the test there shall be no damage to impair the further use of the access cover.
9.108 Additional requirements for service units intended to be installed onfloor are given in
IEC 61084-2-4:2017.
10 Mechanical properties
This clause of Part 1 is applicable, except as follows:
10.1 Mechanical strength
Replacement:
Underfloor, flushfloor and onfloor CTS/CDS shall have adequate mechanical strength.
Compliance is checked by the tests specified in 10.3 and 10.5 according to Annex AA.
10.2 Cable support test
Not applicable.
10.3 Impact test
10.3.2 Impact test for installation and application
Additional subclauses:
10.3.2.101 Systems components only intended to be mounted underfloor are not tested. The
test is carried out on an assembly made of one or more trunking lengths or ducting lengths
with the relevant system component, if any, to fulfil the various functions of the system and
prepared according
...