SIST EN IEC 61084-2-2:2024/A11:2024
(Amendment)Cable trunking systems and cable ducting systems for electrical installations - Part 2-2: Particular requirements - Part 2-2: Particular requirements - Cable trunking systems and cable ducting systems intended for mounting underfloor, flushfloor, or onfloor
Cable trunking systems and cable ducting systems for electrical installations - Part 2-2: Particular requirements - Part 2-2: Particular requirements - Cable trunking systems and cable ducting systems intended for mounting underfloor, flushfloor, or onfloor
Common modifications for the adoption as a European Standard of IEC 61084-2-2:2017 ed 2.0 (PR= 72101).
Elektroinstallationskanalsysteme für elektrische Installationen - Teil 2-2: Besondere Anforderungen für Elektroinstallationskanalsysteme für die Montage unterboden, bodenbündig, oder aufboden
Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques - Partie 2-2: Exigences particulières - Systèmes de goulottes et systèmes de conduits-profilés prévus pour être montés en sous-sol, encastrés dans le sol, ou sur le sol
Sistemi kabelskih korit in sistemi kabelskih cevi za električne inštalacije - 2-2. del: Posebne zahteve - Sistemi kabelskih korit in sistemi kabelskih cevi, namenjenih za montažo pod tlemi, po golih tleh ali po tleh - Dopolnilo A11
General Information
- Status
- Published
- Public Enquiry End Date
- 28-Feb-2023
- Publication Date
- 18-Sep-2024
- Technical Committee
- I11 - Imaginarni 11
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 18-Sep-2024
- Due Date
- 23-Nov-2024
- Completion Date
- 19-Sep-2024
Relations
- Effective Date
- 01-Nov-2024
Overview
SIST EN IEC 61084-2-2:2024/A11:2024 is the Slovenian adoption of the European Standard EN IEC 61084-2-2:2024 with amendment A11. This standard specifies particular requirements for cable trunking systems (CTS) and cable ducting systems (CDS) intended for electrical installations. It focuses on systems designed for mounting underfloor, flushfloor, or onfloor, providing standardized criteria for their construction, performance, and compliance, especially when integrated into modern building infrastructure. The amendment A11 introduces common European modifications, ensuring harmonization with international practices and EU directives.
Key Topics
Scope and Application
The standard addresses safety and functional requirements for cable trunking and ducting systems installed:- Underfloor (beneath surface flooring)
- Flushfloor (level with the finished floor)
- Onfloor (fixed directly on the floor surface)
Mechanical Properties
Guidelines for mechanical strength are revised, including impact resistance during installation and service life. There is a focus on ensuring that damage, such as sharp edges from impacts, does not compromise electrical safety or damage installed conductors.Compliance Transition
Annex C details compliance checks for systems previously certified to EN 50085-2-2:2008, outlining when additional testing is-or is not-required for updating to the newer standard.Special National Conditions
The document addresses special national installation requirements, allowing for adaptations due to local practices, climatic conditions, or regulatory constraints, such as specific rules for the closure of cable openings in certain countries.Harmonization with EU Safety Objectives
Annex ZZ demonstrates how the standard aligns with the Low Voltage Directive 2014/35/EU, supporting presumption of conformity for electrical equipment safety objectives in the European Union.
Applications
SIST EN IEC 61084-2-2:2024/A11:2024 is essential for:
Building and Infrastructure Projects
Ensuring safe, robust cable management in commercial and residential settings where power, data, and communication cables are routed under, in, or on floors.Electrical Contractors and Engineers
Supporting compliant installation practices for floor-mounted cable trunking and ducting systems in new builds, renovations, and refits.Manufacturers and Product Developers
Providing the criteria needed for product design, testing, and documentation, especially for products targeting European markets.Regulatory Compliance
Aiding compliance with EU directives, national laws, and industry best practices concerning cable containment, safety from mechanical damage, ingress protection, fire safety, and environmental characteristics.
Related Standards
- EN IEC 61084-1:2024 & EN IEC 61084-1:2024/A11:2024
- General requirements for cable trunking and cable ducting systems for electrical installations.
- EN 50085-2-2:2008
- Earlier standard for similar systems, referenced for transitional compliance checks.
- IEC 60068 Series
- Environmental testing standards relevant to corrosion and impact resistance.
- Directive 2014/35/EU (Low Voltage Directive)
- European legislation on electrical equipment safety within specified voltage limits.
By ensuring alignment with SIST EN IEC 61084-2-2:2024/A11:2024, stakeholders in the electrical installation sector can facilitate safe, standardized, and future-proof solutions for cable management within floor-mounted contexts across Europe.
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
SIST EN IEC 61084-2-2:2024/A11:2024 is a amendment published by the Slovenian Institute for Standardization (SIST). Its full title is "Cable trunking systems and cable ducting systems for electrical installations - Part 2-2: Particular requirements - Part 2-2: Particular requirements - Cable trunking systems and cable ducting systems intended for mounting underfloor, flushfloor, or onfloor". This standard covers: Common modifications for the adoption as a European Standard of IEC 61084-2-2:2017 ed 2.0 (PR= 72101).
Common modifications for the adoption as a European Standard of IEC 61084-2-2:2017 ed 2.0 (PR= 72101).
SIST EN IEC 61084-2-2:2024/A11:2024 is classified under the following ICS (International Classification for Standards) categories: 29.060.01 - Electrical wires and cables in general; 29.120.10 - Conduits for electrical purposes. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN IEC 61084-2-2:2024/A11:2024 has the following relationships with other standards: It is inter standard links to SIST EN IEC 61084-2-2:2024. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
SIST EN IEC 61084-2-2:2024/A11:2024 is associated with the following European legislation: EU Directives/Regulations: 2014/35/EU; Standardization Mandates: M/511. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
SIST EN IEC 61084-2-2:2024/A11:2024 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
01-november-2024
Sistemi kabelskih korit in sistemi kabelskih cevi za električne inštalacije - 2-2. del:
Posebne zahteve - Sistemi kabelskih korit in sistemi kabelskih cevi, namenjenih za
montažo pod tlemi, po golih tleh ali po tleh - Dopolnilo A11
Cable trunking systems and cable ducting systems for electrical installations - Part 2-2:
Particular requirements - Part 2-2: Particular requirements - Cable trunking systems and
cable ducting systems intended for mounting underfloor, flushfloor, or onfloor
Elektroinstallationskanalsysteme für elektrische Installationen - Teil 2-2: Besondere
Anforderungen für Elektroinstallationskanalsysteme für die Montage unterboden,
bodenbündig, oder aufboden
Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques -
Partie 2-2: Exigences particulières - Systèmes de goulottes et systèmes de conduits-
profilés prévus pour être montés en sous-sol, encastrés dans le sol, ou sur le sol
Ta slovenski standard je istoveten z: EN IEC 61084-2-2:2024/A11:2024
ICS:
29.120.10 Inštalacijske cevi za Conduits for electrical
električne namene purposes
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN IEC 61084-2-2:2024/A11
NORME EUROPÉENNE
EUROPÄISCHE NORM September 2024
ICS 29.060.01; 29.120.10
English Version
Cable trunking systems and cable ducting systems for electrical
installations - Part 2-2: Particular requirements - Cable trunking
systems and cable ducting systems intended for mounting
underfloor, flushfloor, or onfloor
Systèmes de goulottes et systèmes de conduits-profilés Installationskanalsysteme für elektrische Installationen - Teil
pour installations électriques - Partie 2-2: Exigences 2-2: Besondere Anforderungen - Installationskanalsysteme
particulières - Systèmes de goulottes et systèmes de für die Montage unterflur, bodenbündig oder aufflur
conduits-profilés prévus pour être montés en sous-sol,
encastrés dans le sol, ou sur le sol
This amendment A11 modifies the European Standard EN IEC 61084-2-2:2024; it was approved by CENELEC on 2024-08-05. CENELEC
members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this amendment the
status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as
the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61084-2-2:2024/A11:2024 E
Contents Page
1 Modification to Clause 10 “Mechanical properties” . 4
2 Addition of Annex C, “Compliance checks to be carried out for cable trunking systems
and cable ducting systems currently complying with EN 50085-2-2:2008 in order to
comply with EN IEC 61084-2-2:2024”. 5
3 Addition of Annex ZA, “Normative references to international publications with their
corresponding European publications” . 8
4 Addition of Annex ZB, “Special national conditions” . 9
5 Addition of Annex ZZ, “Relationship between this European standard and the safety
objectives of Directive 2014/35/EU [2014 OJ L96] aimed to be covered” . 10
European foreword
This document (EN IEC 61084-2-2:2024/A11:2024) has been prepared by CLC/TC 213 “Cable management
systems”.
The following dates are fixed:
• latest date by which this document has (dop) 2025-08-05
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2029-08-05
standards conflicting with this document
have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document is used in conjunction with EN IEC 61084-1:2024 and EN IEC 61084-1:2024/A11:2024.
This document has been prepared under a standardization request addressed to CENELEC by the European
Commission. The Standing Committee of the EFTA States subsequently approves these requests for its
Member States.
For the relationship with EU Legislation, see informative Annex ZZ, which is an integral part of this document.
Any feedback and questions on this document should be directed to the users’ national committee. A complete
listing of these bodies can be found on the CENELEC website.
1 Modification to Clause 10 “Mechanical properties”
In 10.3.2.104, replace the NOTE with
“The assembly is opened to check that any internal cracks do not impair electrical safety.
NOTE Electrical safety can be impaired when the impact creates a sharp edge which can damage insulated conductors
or cables (see 9.1).”
2 Addition of Annex C, “Compliance checks to be carried out for cable trunking
systems and cable ducting systems currently complying with EN 50085-2-2:2008
in order to comply with EN IEC 61084-2-2:2024”
Add the following Annex C:
“
Annex C
(normative)
Compliance checks to be carried out for cable trunking systems and
cable ducting systems currently complying with EN 50085-2-2:2008 in
order to comply with EN IEC 61084-2-2:2024
This normative annex relates to EN IEC 61084-2-2:2024 requirements. It informs where compliance checks are
required and where compliance checks are not required to be carried out in order that cable trunking systems
and cable ducting systems can be declared to meet the requirements of EN IEC 61084-2-2:2024 if they already
comply with EN 50085-2-2:2008.
Table C.1 — Required compliance checks
Test Description Compliance check
reference
subclause
Marking and documentation
7.1 Marking of system components Not required
7.2 Durability and legibility of marking Not required
7.3 Documentation Not required
7.4 Symbols Not required
7.101 Marking of access units and service units suitable for dry Not required
treatment of floor only
7.102 Marking of service units Not required
7.103 Compliance with 7.101 and 7.102 Not required
Construction
9.1 Sharp edges N
...