ISO 7240-11:2011
(Main)Fire detection and alarm systems — Part 11: Manual call points
Fire detection and alarm systems — Part 11: Manual call points
ISO 7240-11:2011 specifies the requirements, test methods and performance criteria for manual call points in fire detection and alarm systems in and around buildings (see ISO 7240‑1). It takes into account indoor and outdoor conditions, the appearance and operation of the manual call points for type A "direct operation" and type B "indirect operation", and covers those which are simple mechanical switches, those which are fitted with simple electronic components (e.g. resistors, diodes) and those which contain active electronic components and which work with the control and indicating equipment for signalling and identifying, for example, an address or location. ISO 7240-11:2011 does not cover manual call points for special applications, for example manual call points that are intrinsically safe or for use in hazardous conditions, if such applications require additional or other requirements or tests than those given in ISO 7240-11:2011.
Systèmes de détection et d'alarme d'incendie — Partie 11: Déclencheurs manuels d'alarme
General Information
Relations
Standards Content (Sample)
INTERNATIONAL ISO
STANDARD 7240-11
Second edition
2011-06-15
Fire detection and alarm systems —
Part 11:
Manual call points
Systèmes de détection et d'alarme d'incendie —
Partie 11: Déclencheurs manuels d'alarme
Reference number
©
ISO 2011
© ISO 2011
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2011 – All rights reserved
Contents Page
Foreword .iv
Introduction.vi
1 Scope.1
2 Normative references.1
3 Terms and definitions .2
4 Requirements.3
4.1 Compliance .3
4.2 Marking and data .3
4.3 Frangible element.4
4.4 Indicators for alarm condition.5
4.5 Reset facility .5
4.6 Test facility.5
4.7 Construction and design .5
4.8 Requirements for software controlled manual call points.10
5 Tests .12
5.1 General .12
5.2 Operational performance.14
5.3 Function test .16
5.4 Test facility test (operational) .16
5.5 Reliability (endurance).17
5.6 Variation of supply parameters.17
5.7 Dry heat (operational) .18
5.8 Dry heat (endurance).19
5.9 Cold (operational).20
5.10 Damp heat, cyclic (operational) .21
5.11 Damp heat, cyclic (endurance) .22
5.12 Damp heat, steady state (endurance).22
5.13 SO corrosion (endurance) .23
5.14 Shock (operational) .24
5.15 Impact (operational) .25
5.16 Vibration, sinusoidal (operational) .26
5.17 Vibration, sinusoidal (endurance) .27
5.18 Electromagnetic compatibility (EMC) (operational).28
5.19 Enclosure protection.29
5.20 Exposure to simulated solar radiation (endurance) .30
6 Test report.31
Annex A (normative) Test apparatus for test of operation.32
Annex B (informative) Test apparatus for test for non-operation.34
Annex C (informative) Apparatus for impact test .35
Bibliography.39
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 7240-11 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting,
Subcommittee SC 3, Fire detection and alarm systems.
This second edition cancels and replaces the first edition (ISO 7240-11:2005), which has been technically
revised. It also incorporates the Amendment ISO 7240-11:2005/Amd.1:2009.
ISO 7240 consists of the following parts, under the general title Fire detection and alarm systems:
⎯ Part 1: General and definitions
⎯ Part 2: Control and indicating equipment
⎯ Part 3: Audible alarm devices
⎯ Part 4: Power supply equipment
⎯ Part 5: Point-type heat detectors
⎯ Part 6: Carbon monoxide fire detectors using electro-chemical cells
⎯ Part 7: Point-type smoke detectors using scattered light, transmitted light or ionization
⎯ Part 8: Carbon monoxide fire detectors using an electro-chemical cell in combination with a heat sensor
⎯ Part 9: Test fires for fire detectors [Technical Specification]
⎯ Part 10: Point-type flame detectors
⎯ Part 11: Manual call points
⎯ Part 12: Line type smoke detectors using a transmitted optical beam
⎯ Part 13: Compatibility assessment of system components
iv © ISO 2011 – All rights reserved
⎯ Part 14: Guidelines for drafting codes of practice for design, installation and use of fire detection and fire
alarm systems in and around buildings [Technical Report]
⎯ Part 15: Point type fire detectors using scattered light, transmitted light or ionization sensors in
combination with a heat sensor
⎯ Part 16: Sound system control and indicating equipment
⎯ Part 17: Short-circuit isolators
⎯ Part 18: Input/output devices
⎯ Part 19: Design, installation, commissioning and service of sound systems for emergency purposes
⎯ Part 20: Aspirating smoke detectors
⎯ Part 21: Routing equipment
⎯ Part 22: Smoke-detection equipment for ducts
⎯ Part 24: Sound-system loudspeakers
⎯ Part 25: Components using radio transmission paths
⎯ Part 27: Point-type fire detectors using a scattered-light, transmitted-light or ionization smoke sensor, an
electrochemical-cell carbon-monoxide sensor and a heat sensor
⎯ Part 28: Fire protection control equipment
A part 23 dealing with visual alarm devices and a part 29 dealing with video fire detectors are under
development.
Introduction
This part of ISO 7240 has been prepared by ISO/TC 21/SC 3, the secretariat of which is held by SA and is
based on ISO 7240-11:2005.
This part of ISO 7240 has been drafted on the basis of appearance and functions that should be provided on
all manual call points for use in fire detection and fire alarm systems. The colours, dimensions, shapes and
methods of operation are based on recognized operating principles that give confidence and recognition to the
user when operating in genuine fire alarm situations.
The purpose of a manual call point is to enable a person discovering a fire to initiate the operation of a fire
alarm system so that appropriate measures can be taken.
It is important for manual call points to be recognizable and simple to use, without the requirement to read
elaborate instructions so that anyone discovering a fire is able to use the manual call point without previous
familiarity with it.
The intention of this part of ISO 7240 is to specify requirements for operation and reliability. The methods of
operation of the manual call points covered are as follows:
⎯ type A: direct operation (single action);
⎯ type B: indirect operation (double action).
Both types require the breaking or the visible displacement by change of the position of a frangible element
forming part of the front face, which is considered as the most suitable method for general application and
which acts as a deterrent to the misuse of the device.
Importance has been placed on identifying the manual call point, the method by which it is activated and an
indication to the user that the initiation of an alarm has been given.
The resulting part of ISO 7340 takes into account national variances in custom and practice and language in
bringing together common elements that contribute towards a standard device for use throughout the world.
The performance of manual call points is assessed from results obtained in specific tests. This part of
ISO 7240 is not intended to place any other restrictions on the design and construction of such manual call
points.
vi © ISO 2011 – All rights reserved
INTERNATIONAL STANDARD ISO 7240-11:2011(E)
Fire detection and alarm systems —
Part 11:
Manual call points
1 Scope
This part of ISO 7240 specifies the requirements, test methods and performance criteria for manual call points
in fire detection and alarm systems in and around buildings (see ISO 7240-1). It takes into account indoor and
outdoor conditions, the appearance and operation of the manual call points for type A “direct operation” and
type B “indirect operation”, and covers those which are simple mechanical switches, those which are fitted
with simple electronic components (e.g. resistors, diodes) and those which contain active electronic
components and which work with the control and indicating equipment for signalling and identifying, for
example, an address or location.
This part of ISO 7240 does not cover manual call points for special applications, for example manual call
points that are intrinsically safe or for use in hazardous conditions, if such applications require additional or
other requirements or tests than those given in this part of ISO 7240.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
ISO 209, Aluminium and aluminium alloys — Chemical composition
ISO 3098-0:1997, Technical product documentation — Lettering — Part 0: General requirements
ISO 3864-1, Graphical symbols — Safety colours and safety signs — Part 1: Design principles for safety signs
and safety markings
ISO 7240-1, Fire detection and alarm systems — Part 1: General and definition
ISO 7240-2, Fire detection and alarm systems — Part 2: Control and indicating equipment
IEC 60068-1, Environmental testing — Part 1: Genera
...