IEC 61000-6-2:1999
(Main)Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments
Applies to electrical and electronic apparatus intended for use in industrial environments, for which no dedicated product or product-family immunity standard exists. Immunity requirements in the frequency range 0 Hz to 400 GHz are covered, in relation to continuous and transient, conducted and radiated disturbances, including electrostatic discharges. Test requirements are specified for each port considered. Apparatus intended to be used in industrial locations are characterized by the existence of one or more of the following: - a power network exists powered by a high or medium voltage power transformer dedicated for the supply of an installation feeding manufacturing or similar plant; - industrial, scientific and medical (ISM) apparatus; - heavy inductive or capacitive loads are frequently switched; - currents and associated magnetic fields are high.
Compatibilité électromagnétique (CEM) - Partie 6-2: Normes génériques - Immunité pour les environnements industriels
S'applique aux appareils électriques et électroniques destinés à être utilisés dans les environnements industriels, pour lesquels aucune norme d'immunité spécifique à un produit ou à une famille de produits n'existe. Cette norme couvre les exigences d'immunité dans la gamme de fréquences de 0 Hz à 400 GHz, en rapport avec les perturbations continues et transitoires, conduites et rayonnées, y compris les décharges électrostatiques. Les prescriptions d'essais sont spécifiées pour chaque accès considéré. Les appareils destinés à être utilisés dans des sites industriels sont caractérisés par l'existence d'une ou plusieurs des conditions suivantes: - existence d'une installation de puissance alimentée par un transformateur de puissance haute ou moyenne tension, réservé à l'alimentation d'une installation alimentant un site industriel ou analogue; - présence d'appareils industriels, scientifiques et médicaux (ISM); - commutations fréquentes de charges inductives ou capacitives importantes; - valeurs élevées des courants et des champs magnétiques associés.
General Information
Relations
Standards Content (Sample)
NORME
CEI
INTERNATIONALE
IEC
61000-6-2
INTERNATIONAL
Première édition
STANDARD
First edition
1999-01
Compatibilité électromagnétique (CEM) –
Partie 6-2:
Normes génériques –
Immunité pour les environnements industriels
Electromagnetic compatibility (EMC) –
Part 6-2:
Generic standards –
Immunity for industrial environments
Numéro de référence
Reference number
CEI/IEC 61000-6-2:1999
Numéros des publications Numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60 000. issued with a designation in the 60 000 series.
Publications consolidées Consolidated publications
Les versions consolidées de certaines publications de Consolidated versions of some IEC publications
la CEI incorporant les amendements sont disponibles. including amendments are available. For example,
Par exemple, les numéros d’édition 1.0, 1.1 et 1.2 edition numbers 1.0, 1.1 and 1.2 refer, respectively, to
indiquent respectivement la publication de base, la the base publication, the base publication incor-
publication de base incorporant l’amendement 1, et porating amendment 1 and the base publication
la publication de base incorporant les amendements 1 incorporating amendments 1 and 2.
et 2.
Validité de la présente publication Validity of this publication
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept under
constamment revu par la CEI afin qu'il reflète l'état constant review by the IEC, thus ensuring that the
actuel de la technique. content reflects current technology.
Des renseignements relatifs à la date de re- Information relating to the date of the reconfirmation of
confirmation de la publication sont disponibles dans the publication is available in the IEC catalogue.
le Catalogue de la CEI.
Les renseignements relatifs à des questions à l’étude et Information on the subjects under consideration and
des travaux en cours entrepris par le comité technique work in progress undertaken by the technical com-
qui a établi cette publication, ainsi que la liste des mittee which has prepared this publication, as well as
publications établies, se trouvent dans les documents the list of publications issued, is to be found at the
ci-dessous: following IEC sources:
• «Site web» de la CEI* • IEC web site*
• Catalogue des publications de la CEI • Catalogue of IEC publications
Publié annuellement et mis à jour régulièrement Published yearly with regular updates
(Catalogue en ligne)* (On-line catalogue)*
• Bulletin de la CEI • IEC Bulletin
Disponible à la fois au «site web» de la CEI* Available both at the IEC web site* and
et comme périodique imprimé as a printed periodical
Terminologie, symboles graphiques Terminology, graphical and letter
et littéraux symbols
En ce qui concerne la terminologie générale, le lecteur For general terminology, readers are referred to
se reportera à la CEI 60050: Vocabulaire Electro- IEC 60 050: International Electrotechnical Vocabulary
technique International (VEI). (IEV).
Pour les symboles graphiques, les symboles littéraux For graphical symbols, and letter symbols and signs
et les signes d'usage général approuvés par la CEI, le approved by the IEC for general use, readers are
lecteur consultera la CEI 60027: Symboles littéraux à referred to publications IEC 60027: Letter symbols to
utiliser en électrotechnique, la CEI 60417: Symboles be used in electrical technology, IEC 60417: Graphical
graphiques utilisables sur le matériel. Index, relevé et symbols for use on equipment. Index, survey and
compilation des feuilles individuelles, et la CEI 60617: compilation of the single sheets and IEC 60617:
Symboles graphiques pour schémas. Graphical symbols for diagrams.
* Voir adresse «site web» sur la page de titre. * See web site address on title page.
NORME
CEI
INTERNATIONALE
IEC
61000-6-2
INTERNATIONAL
Première édition
STANDARD
First edition
1999-01
Compatibilité électromagnétique (CEM) –
Partie 6-2:
Normes génériques –
Immunité pour les environnements industriels
Electromagnetic compatibility (EMC) –
Part 6-2:
Generic standards –
Immunity for industrial environments
IEC 1999 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in
utilisée sous quelque forme que ce soit et par aucun any form or by any means, electronic or mechanical,
procédé, électronique ou mécanique, y compris la photo- including photocopying and microfilm, without permission in
copie et les microfilms, sans l'accord écrit de l'éditeur. writing from the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
PRICE CODE N
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61000-6-2 © CEI:1999
SOMMAIRE
Pages
AVANT-PROPOS . 4
INTRODUCTION .6
Articles
1 Domaine d'application et objet. 8
2 Références normatives.10
3 Définitions.12
4 Critères d'aptitude à la fonction . 14
5 Conditions pendant les essais . 14
6 Documentation du produit. 16
7 Applicabilité.16
8 Exigences pour les essais d'immunité. 16
Tableau 1 – Immunité – Accès par l’enveloppe. 18
Tableau 2 – Immunité – Accès signaux . 20
Tableau 3 – Immunité – Accès d'entrée et de sortie de puissance en courant continu. 22
Tableau 4 – Immunité – Accès d'entrée et de sortie de puissance en courant alternatif . 24
Tableau 5 – Immunité – Accès par la borne de terre fonctionnelle . 26
61000-6-2 © IEC:1999 – 3 –
CONTENTS
Page
FOREWORD . 5
INTRODUCTION .7
Clause
1 Scope and object . 9
2 Normative references.11
3 Definitions.13
4 Performance criteria.15
5 Conditions during testing . 15
6 Product documentation.17
7 Applicability.17
8 Immunity test requirements . 17
Table 1 – Immunity – Enclosure ports . 19
Table 2 – Immunity – Signal ports . 21
Table 3 – Immunity – Input and output d.c. power ports. 23
Table 4 – Immunity – Input and output a.c. power ports. 25
Table 5 – Immunity – Functional earth ports. 27
– 4 – 61000-6-2 © CEI:1999
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
___________
COMPATIBILITÉ ÉLECTROMAGNÉTIQUE (CEM) –
Partie 6-2: Normes génériques –
Immunité pour les environnements industriels
AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, rapports techniques ou guides et agréés comme tels par les Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme de la CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 61000-6-2 a été établie par le comité d'études 77 de la CEI:
Compatibilité électromagnétique.
Cette norme tient compte du projet de Norme européenne prEN 50082-2 (août 1996) élaboré
par le comité technique 210 du CENELEC: CEM.
Le texte de cette norme est basé sur les documents suivants:
FDIS Rapport de vote
77/208/FDIS 77/211/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
61000-6-2 © IEC:1999 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –
Part 6-2: Generic standards –
Immunity for industrial environments
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-6-2 has been prepared by IEC technical committee 77:
Electromagnetic compatibility.
It takes into account the draft European Standard prEN 50082-2 (August 1996), drawn up by
CENELEC technical committee 210: EMC.
The text of this standard is based on the following documents:
FDIS Report on voting
77/208/FDIS 77/211/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
– 6 – 61000-6-2 © CEI:1999
INTRODUCTION
La CEI 61000 est publiée sous la forme de plusieurs parties séparées conformément à la
structure suivante.
Partie 1: Généralités
Considérations générales (introduction, principes fondamentaux)
Définitions, terminologie
Partie 2: Environnement
Description de l’environnement
Classification de l’environnement
Niveaux de compatibilité
Partie 3: Limites
Limites d’émission
Limites d’immunité (dans la mesure où ces limites ne relèvent pas des comités de produits)
Partie 4: Techniques d’essai et de mesure
Techniques de mesure
Techniques d’essai
Partie 5: Guides d’installation et d’atténuation
Guides d’installation
Méthodes et dispositifs d’atténuation
Partie 6: Normes génériques
Partie 9: Divers
Chaque partie est à son tour subdivisée en plusieurs parties publiées soit comme Normes
internationales, soit comme rapports techniques, dont certaines ont déjà été publiées en tant
que sections. D’autres seront publiées avec le numéro de la partie suivi d’un tiret et d’un
second chiffre identifiant la subdivision (exemple: 61000-6-1).
61000-6-2 © IEC:1999 – 7 –
INTRODUCTION
IEC 61000 is published in separate parts according to the following structure:
Part 1: General
General considerations (introduction, fundamental principles)
Definitions, terminology
Part 2: Environment
Description of the environment
Classification of the environment
Compatibility levels
Part 3: Limits
Emission limits
Immunity limits (insofar as these limits do not fall under the responsibility of the product
committees)
Part 4: Testing and measurement techniques
Measurement techniques
Testing techniques
Part 5: Installation and mitigation guidelines
Installation guidelines
Mitigation methods and devices
Part 6: Generic standards
Part 9: Miscellaneous
Each part is further subdivided into several parts, published either as International Standards
or technical reports, some of which have already been published as sections. Others will be
published with the part number followed by a dash and a second number identifying the
subdivision (example: 61000-6-1).
– 8 – 61000-6-2 © CEI:1999
COMPATIBILITÉ ÉLECTROMAGNÉTIQUE (CEM) –
Partie 6-2: Normes génériques –
Immunité pour les environnements industriels
1 Domaine d'application et objet
La présente partie de la CEI 61000 concernant les exigences d'immunité en matière de
compatibilité électromagnétique s'applique aux appareils électriques et électroniques destinés
à être utilisés dans les environnements industriels, définis ci-dessous, pour lesquels aucune
norme d'immunité spécifique à un produit ou à une famille de produits n'existe.
Cette norme couvre les exigences d'immunité dans la gamme de fréquences de 0 Hz à
400 GHz. Il n'est pas nécessaire d'effectuer des essais aux fréquences pour lesquelles aucune
exigence n'est spécifiée.
Lorsqu'il existe une norme d'immunité spécifique à un produit ou à une famille de produits,
cette norme prévaut sur tous les aspects de la présente norme générique.
Les environnements couverts par cette norme sont les environnements industriels, intérieurs et
extérieurs. Les appareils couverts par cette norme sont destinés à être raccordés à un réseau
d'énergie alimenté par un transformateur haute tension ou moyenne tension réservé à
l'alimentation d'une l'installation alimentant un site industriel ou analogue, et destinés à
fonctionner à l’intérieur ou à proximité des sites industriels, comme défini ci-dessous.
Les appareils destinés à être utilisés dans des sites industriels sont caractérisés par
l’existence d’une ou plusieurs des conditions suivantes:
– existence d'une installation de puissance alimentée par un transformateur de puissance
haute ou moyenne tension, réservé à l’alimentation d’une installation alimentant un site
industriel ou analogue;
1)
– présence d'appareils industriels, scientifiques et médicaux (ISM)
– commutations fréquentes de charges inductives ou capacitives importantes;
– valeurs élevées des courants et des champs magnétiques associés.
L'objet de cette norme est de définir les prescriptions concernant les essais d'immunité aux
perturbations continues et transitoires, conduites et rayonnées, y compris aux décharges
électrostatiques, pour les appareils définis dans le domaine d'application.
Les exigences d'immunité ont été choisies pour assurer un niveau adéquat d'immunité pour les
appareils utilisés sur des sites industriels. Ces niveaux ne couvrent pas, cependant, les cas
extrêmes qui peuvent apparaître, mais avec une très faible probabilité, sur un site quelconque.
Cette norme n'inclut pas, pour les besoins des essais, tous les phénomènes perturbateurs
mais uniquement ceux considérés comme applicables pour les appareils couverts par la
norme.
Les prescriptions d'essais sont spécifiées pour chaque accès considéré.
NOTE 1 – Cette norme ne couvre pas les considérations relatives à la sécurité.
NOTE 2 – Dans des cas spéciaux, des situations peuvent apparaître dans lesquelles les niveaux de perturbation
peuvent dépasser les niveaux spécifiés dans cette norme, par exemple lorsqu'un appareil est installé à proximité
___________
1)
Tels que définis dans le CISPR 11, ISM classe A.
61000-6-2 © IEC:1999 – 9 –
ELECTROMAGNETIC COMPATIBILITY (EMC) –
Part 6-2: Generic standards –
Immunity for industrial environments
1 Scope and object
This part of IEC 61000 for EMC immunity requirements applies to electrical and electronic
apparatus intended for use in industrial environments, as described below, for which no
dedicated product or product-family immunity standard exists.
Immunity requirements in the frequency range 0 Hz to 400 GHz are covered. No tests need to
be performed at frequencies where no requirements are specified.
Where a relevant dedicated product or product-family EMC immunity standard exists, it will
take precedence over all aspects of this generic standard.
The environments encompassed by this standard are industrial, both indoor and outdoor.
Apparatus covered by this standard is intended to be connected to a power network supplied
from a high or medium voltage transformer dedicated to the supply of an installation feeding
manufacturing or similar plant, and intended to operate in or in proximity to industrial locations,
as described below.
Apparatus intended to be used in industrial locations are characterized by the existence of one
or more of the following:
– a power network exists powered by a high or medium voltage power transformer dedicated
for the supply of an installation feeding manufacturing or similar plant;
1)
– industrial, scientific and medical (ISM) apparatus;
– heavy inductive or capacitive loads are frequently switched;
– currents and associated magnetic fields are high.
The object of this standard is to define immunity test requirements for apparatus defined in the
scope in relation to continuous and transient, conducted and radiated disturbances, including
electrostatic discharges.
The immunity requirements have been selected to ensure an adequate level of immunity for
apparatus at industrial locations. The levels do not, however, cover extreme cases, which may
occur at any location, but with an extremely low probability of occurrence. Not all disturbance
phenomena have been included for testing purposes in this standard, but only those
considered as relevant for the equipment covered by this standard.
Test requirements are specified for each port considered.
NOTE 1 – Safety considerations are not covered by this standard.
NOTE 2 – In special cases, situations will arise where the level of disturbances may exceed the levels specified in
this standard e.g. where an apparatus is installed in proximity to ISM equipment as defined in CISPR 11 or where
___________
1)
As defined in CISPR 11, ISM class A.
– 10 – 61000-6-2 © CEI:1999
d'un appareil ISM tel que défini dans le CISPR 11 ou lorsqu’un émetteur portable est utilisé très près d’un appareil.
Dans ces cas, des moyens spéciaux d'atténuation peuvent être nécessaires.
NOTE 3 – L'environnement industriel peut être modifié par des moyens spéciaux d'atténuation. Lorsqu'il peut être
démontré que ces moyens produisent un environnement électromagnétique équivalent à l'environnement résidentiel
ou commercial, ou à l'environnement pour l'industrie légère, il convient alors d’appliquer la norme générique pour
cet environnement ou la norme de produit applicable.
2 Références normatives
Les documents normatifs suivants contiennent des dispositions qui, par suite de la référence
qui y est faite, constituent des dispositions valables pour la présente Norme internationale.
Pour les références datées, les amendements ultérieurs ou les révisions de ces publications ne
s’appliquent pas. Toutefois, les parties prenantes aux accords fondés sur la présente Norme
internationale sont invitées à rechercher la possibilité d'appliquer les éditions les plus récentes
des documents normatifs indiqués ci-après. Pour les références non datées, la dernière édition
du document normatif en référence s’applique. Les membres de la CEI et de l'ISO possèdent
le registre des Normes internationales en vigueur.
CEI 60050(161):1990, Vocabulaire Electrotechnique International (VEI) – Chapitre 161:
Compatibilité électromagnétique
CEI 61000-4-2:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 2: Essai d’immunité aux décharges électrostatiques – Publication
fondamentale en CEM
CEI 61000-4-3:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 3: Essai d’immunité aux champs électromagnétiques rayonnés aux
fréquences radioélectriques
CEI 61000-4-4:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 4: Essais d’immunité aux transitoires électriques rapides en salves –
Publication fondamentale en CEM
CEI 61000-4-5:1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 5: Essai d’immunité aux ondes de choc
CEI 61000-4-6:1996, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 6: Immunité aux perturbations conduites, induites par les champs
radioélectriques
CEI 61000-4-8:1993, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 8: Essai d’immunité au champ magnétique à la fréquence du réseau –
Publication fondamentale en CEM
CEI 61000-4-11:1994, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d’essai et
de mesure – Section 11: Essais d’immunité aux creux de tension, coupures brèves et
variations de tension
CISPR 11:1997, Appareils industriels, scientifiques et médicaux (ISM) à fréquence radio-
électrique – Caractéristiques de perturbations électromagnétiques – Limites et méthodes de
mesure
CISPR 22:1997, Appareils de traitement de l’information – Caractéristiques de perturbations
radioélectriques – Limites et méthodes de mesure
61000-6-2 © IEC:1999 – 11 –
a hand-held transmitter is used in close proximity to an apparatus. In these instances, special mitigation measures
may have to be employed.
NOTE 3 – The industrial environment may be changed by special mitigation measures. Where such measures can
be shown to produce an electromagnetic environment equivalent to the residential, commercial or light-industrial
environment then the generic standard for this environment, or the relevant product standard, should be applied.
2 Normative references
The following normative documents contain provisions which, through reference in this text,
constitute provisions of this International Standard. For dated references, subsequent
amendments to, or revisions of, any of these publications do not apply. However, parties to
agreements based on this International Standard are encouraged to investigate the possibility
of applying the most recent editions of the normative documents indicated below. For undated
references, the latest edition of the normative document referred to applies. Members of IEC
and ISO maintain registers of currently valid International Standards.
IEC 60050(161):1990, International Electrotechnical Vocabulary (IEV) – Chapter 161: Electro-
magnetic compatibility
IEC 61000-4-2:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 2: Electrostatic discharge immunity test – Basic EMC Publication
IEC 61000-4-3:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 3: Radiated, radio-frequency, electromagnetic field immunity test
IEC 61000-4-4:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 4: Electrical fast transient/burst immunity test – Basic EMC Publication
IEC 61000-4-5:1995, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 5: Surge immunity test
IEC 61000-4-6:1996, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 6: Immunity to conducted disturbances, induced by radio-frequency fields
IEC 61000-4-8:1993, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 8: Power frequency magnetic field immunity test – Basic EMC Publication
IEC 61000-4-11:1994, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement
techniques – Section 11: Voltage dips, short interruptions and voltage variations immunity tests
CISPR 11:1997, Industrial, scientific and medical (ISM) radio-frequency equipment – Electro-
magnetic disturbance characteristics – Limits and methods of measurement
CISPR 22:1997, Information technology equipment – Radio disturbance characteristics – Limits
and methods of measurement
– 12 – 61000-6-2 © CEI:1999
3 Définitions
Les définitions concernant la compatibilité électromagnétique (CEM) et les phénomènes
correspondants figurent dans la CEI 60050(161) ainsi que dans d’autres publications de la CEI
et du CISPR.
Les définitions particulières suivantes sont utilisées dans la présente norme:
3.1
accès
interface particulière de l'appareil spécifié avec l'environnement électromagnétique extérieur
(voir figure 1)
Accès par l’enveloppe
Accès signal Accès de puissance
en courant alternatif
Appareil
Accès par la borne de terre Accès de puissance
fonctionnelle en courant continu
IEC 096/99
Figure 1 – Exemples d'accès
3.2
accès par l'enveloppe
frontière physique de l'appareil à travers laquelle les champs électromagnétiques peuvent
rayonner ou à laquelle ils peuvent se heurter
3.3
accès par les câbles
point par lequel un conducteur ou un câble est connecté à l'appareil. Des exemples sont les
accès signaux utilisés pour le transfert de données
3.4
accès par la borne de terre fonctionnelle
accès par les câbles autre qu’un accès signal, de contrôle ou de puissance, connecté à la terre
dans un but autre que la sécurité électrique
3.5
accès signal
accès par lequel un conducteur ou un câble transportant des informations pour le transfert de
données est relié à l’appareil. Des exemples sont les bus de données, les réseaux de
communication, les réseaux de contrôle
3.6
accès de puissance
point par lequel un conducteur ou un câble transportant la puissance électrique primaire
nécessaire pour le fonctionnement de l’appareil ou d’un appareil associé est relié à l’appareil
61000-6-2 © IEC:1999 – 13 –
3 Definitions
Definitions related to EMC and to relevant phenomena are given in IEC 60050(161) and in
other IEC and CISPR publications.
The following particular definitions are used in this standard.
3.1
port
particular interface of the specified apparatus with the external electromagnetic environment
(see figure 1)
Enclosure port
Signal port AC power port
Apparatus
Functional earth port DC power port
IEC 096/99
Figure 1 – Examples of ports
3.2
enclosure port
physical boundary of the apparatus which electromagnetic fields may radiate through or
impinge on
3.3
cable port
port at which a conductor or a cable is connected to the apparatus. Examples are signal ports
used for the transfer of data
3.4
functional earth port
cable port other than signal, control or power port, intended for connection to earth for
purposes other than electrical safety
3.5
signal port
port at which a conductor or cable carrying information for transferring data is connected to the
apparatus. Examples are data buses, communication networks, control networks
3.6
power port
point at which a conductor or cable carrying the primary electrical power needed for the
operation (functioning) of an apparatus or associated apparatus is connected to the apparatus
– 14 – 61000-6-2 © CEI:1999
4 Critères d'aptitude à la fonction
La variété et la diversité des appareils couverts par le domaine d'application de la présente
norme rendent difficile la définition de critères précis pour l'évaluation des résultats des essais
d'immunité.
Si l'appareil devient dangereux ou non sûr suite à l'application des essais définis par la
présente norme, il doit être considéré comme n'ayant pas satisfait à l'essai.
Une description fonctionnelle et une définition des critères d'aptitude à la fonction, pendant ou
après les essais de CEM, doivent être fournies par le fabricant et notées dans le rapport
d'essai sur la base des critères d'aptitude à la fonction suivants.
4.1 Critère d'aptitude A
L'appareil doit continuer à fonctionner comme prévu pendant et après l'essai. Aucune
dégradation du fonctionnement ni perte de fonction n'est autorisée au-dessous du niveau
d'aptitude spécifié par le fabricant lorsque l'appareil est utilisé comme prévu. Le niveau d'apti-
tude peut être remplacé par une perte d'aptitude admissible. Si le niveau minimal d'aptitude ou
la perte d'aptitude admissible ne sont pas spécifiés par le fabricant, ils peuvent être déduits de
la description et de la documentation du produit et de ce que l'utilisateur est raisonnablement
en droit d'attendre de l'appareil si celui-ci est utilisé comme prévu.
4.2 Critère d'aptitude B
L'appareil doit continuer à fonctionner comme prévu après l'essai. Aucune dégradation du
fonctionnement ni perte de fonction n'est autorisée au-dessous du niveau d'aptitude spécifié
par le fabricant, lorsque l'appareil est utilisé comme prévu. Le niveau d'aptitude peut être
remplacé par une perte d'aptitude admissible. Pendant l'essai, une dégradation de fonction-
nement est toutefois autorisée. Aucune modification du mode de fonctionnement en cours ou
des données mémorisées n'est autorisée. Si le niveau minimal d'aptitude ou la perte d'aptitude
admissible ne sont pas spécifiés par le fabricant, ils peuvent être déduits de la description et
de la documentation du produit, et de ce que l'utilisateur est raisonnablement en droit
d'attendre de l'appareil si celui-ci est utilisé comme prévu.
4.3 Critère d'aptitude C
Une perte de fonction temporaire est admise, à condition que cette fonction soit auto-
récupérable ou puisse être rétablie par une intervention sur les commandes.
5 Conditions pendant les essais
L’appareil doit être testé dans le mode de fonctionnement conduisant à la susceptibilité la plus
grande correspondant aux applications normales. On doit faire varier la configuration de
l'échantillon en essai pour obtenir la susceptibilité maximale correspondant aux applications
typiques et aux pratiques d’installation.
Si l'appareil fait partie d'un système, ou peut être connecté à des appareils auxiliaires, il doit
être essayé dans la configuration représentative minimale des appareils auxiliaires permettant
l'essai aux accès d'une manière analogue à celle décrite dans le CISPR 22.
Dans le cas où les instructions d’installation données par le fabricant exigent l'utilisation de
dispositifs ou de mesures de protection externes qui sont clairement spécifiés dans le manuel
destiné aux utilisateurs, les essais doivent être effectués avec les dispositifs ou les mesures
de protection externes mis en oeuvre.
61000-6-2 © IEC:1999 – 15 –
4 Performance criteria
The variety and the diversity of the apparatus within the scope of this standard makes it difficult
to define precise criteria for the evaluation of the immunity test results.
If, as a result of the application of the tests defined in this standard, the apparatus becomes
dangerous or unsafe, the apparatus shall be deemed to have failed the test.
A functional description and a definition of performance criteria, during or as a consequence of
the EMC testing, shall be provided by the manufacturer and noted in the test report, based on
the following criteria.
4.1 Performance criterion A
The apparatus shall continue to operate as intended during and after the test. No degradation
of performance or loss of function is allowed below a performance level specified by the
manufacturer, when the apparatus is used as intended. The performance level may be
replaced by a permissible loss of performance. If the minimum performance level or the
permissible performance loss is not specified by the manufacturer, either of these may be
derived from the product description and documentation, and from what the user may
reasonably expect from the apparatus if used as intended.
4.2 Performance criterion B
The apparatus shall continue to operate as intended after the test. No degradation of
performance or loss of function is allowed below a performance level specified by the
manufacturer, when the apparatus is used as intended. The performance level may be
replaced by a permissible loss of performance. During the test, degradation of performance is
however allowed. No change of actual operating state or stored data is allowed. If the minimum
performance level or the permissible performance loss is not specified by the manufacturer,
either of these may be derived from the product description and documentation, and from what
the user may reasonably expect from the apparatus if used as intended.
4.3 Performance criterion C
Temporary loss of function is allowed, provided the function is self-recoverable or can be
restored by the operation of the controls.
5 Conditions during testing
The equipment under test (EUT) shall be tested in the most susceptible operating mode
consistent with normal applications. The configuration of the test sample shall be varied to
achieve maximum susceptibility consistant with typical applications and installation practice.
If the apparatus is part of a system, or can be connected to auxiliary apparatus, it shall be
tested while connected to the minimum representative configuration of the auxiliary apparatus
necessary to exercise the ports in a similar manner to that described in CISPR 22.
In cases where a manufacturer's installation instructions require the use of external protection
devices or measures which are clearly specified in the user's manual, the tests shall be
performed with the external protection devices or measures in place.
– 16 – 61000-6-2 © CEI:1999
La configuration et le mode de fonctionnement utilisés au cours des essais doivent être notés
avec précision dans le rapport d'essai. Il n'est pas toujours possible d'essayer toutes les
fonctions d'un appareil. Dans ces cas, le ou les modes de fonctionnement les plus critiques
doivent être choisis.
Si l'appareil a un grand nombre d'accès analogues ou d'accès comportant un grand nombre de
connexions analogues, on doit choisir un nombre suffisant de ces accès pour simuler les
conditions de fonctionnement réelles et pour s'assurer que tous les types de terminaison sont
couverts.
Les essais doivent être effectués dans les conditions spécifiées de température, d'humidité et
de pression pour le fonctionnement de l'appareil, et à sa tension assignée d'alimentation, sauf
indication contraire dans la norme fondamentale.
6 Documentation du produit
Si le fabricant utilise sa propre spécification pour obtenir un niveau acceptable de compatibilité
électromagnétique ou de dégradation de la compatibilité électromagnétique, pendant ou après
les essais prescrits par la présente norme, cela doit être indiqué dans la documentation
destinée aux utilisateurs.
7 Applicabilité
L'application des essais pour l'évaluation de l'immunité dépend du type particulier d'appareil,
de sa configuration, de ses accès, de sa technologie et de ses conditions de fonctionnement.
Les essais doivent être appliqués sur les accès appropriés de l'appareil conformément aux
tableaux 1 à 5. Ces essais ne doivent être effectués que lorsque les accès correspondants
existent.
Il peut être déterminé, à partir de l'étude des caractéristiques électriques et de l'usage d'un
appareil particulier, que certains des essais sont inappropriés et, en conséquence, inutiles.
Dans un tel cas, la décision et la justification de ne pas effectuer l'essai doivent être notées
dans le rapport d'essai.
8 Exigences pour les essais d'immunité
Les exigences pour les essais d'immunité des appareils couverts par la présente norme sont
indiquées accès par accès.
Les essais doivent être effectués selon une procédure bien définie et reproductible.
Les essais doivent être effectués successivement, en tant qu'essais indépendants les uns des
autres. La séquence d'essais n'est pas imposée.
La description de l'essai, les caractéristiques du générateur, les méthodes d'essai et
l'installation d'essai sont données dans les normes fondamentales mentionnées dans les
tableaux suivants.
Le contenu de ces normes fondamentales n'est pas répété ici; cependant, des modifications ou
des informations complémentaires pour l'application pratique des essais sont données dans la
présente norme.
61000-6-2 © IEC:1999 – 17 –
The configuration and mode of operation during the tests shall be precisely noted in the test
report. It is not always possible to test every function of the apparatus; in such cases the most
critical mode(s) of operation shall be selected.
If the apparatus has a large number of similar ports or ports with many similar connections, a
sufficient number shall be selected to simulate actual operating conditions and to ensure that
all the different types of termination are covered.
The tests shall be carried out within the operating ranges of temperature, humidity and
pressure specified for the product, and at the rated supply voltage, unless otherwise indicated
in the basic standard.
6 Product documentation
If the manufacturer is using his own specification for an acceptable level of EMC performance
or degradation of EMC performance during or after the testing required by this standard, this
shall be stated in the product documentation available to the user.
7 Applicability
The application of tests for evaluation of immunity depends on the particular apparatus, its
configuration, its ports, its technology and its operating conditions.
Tests shall be applied to the relevant ports of the apparatus according to tables 1 to 5. Tests
shall only be carried out where the relevant ports exist.
It may be determined from consideration of the electrical characteristics and usage of a
particular apparatus that some of the tests are inappropriate and, therefore, unnecessary. In
such a case, it is required that the decision and justification not to test be recorded in the test
report.
8 Immunity test requirements
The immunity test requirements for apparatus covered by this standard are given on a port by
port basis.
Tests shall be conducted in a well-defined and reproducible manner.
The tests shall be carried out individually as single tests in sequence. The sequence of testing
is optional.
The description of the test, the test generator, the test methods and the test set-up to be used
are given in the basic standards which are referred to in the following tables.
The contents of these basic standards are not repeated here; however, modifications or
additional information needed for the practical application of the tests are given in this
standard.
Tableau 1 – Immunité – Accès par l’enveloppe
Phénomènes Spécifications d'essai Unités Normes Remarques Critère
d'environnement fondamentales d'aptitude
1.1 Champ magnétique à la 50, 60 Hz CEI 61000-4-8 L’essai doit être effectué aux fréquences A
fréquence du réseau correspondant à la fréquence de
30 A/m
l’alimentation. Les appareils destinés à être
utilisés dans des zones alimentées à
seulement une de ces fréquences peuvent
n’être essayés qu’à cette fréquence Note 2
Voir note 1
1.2 Champ électromagnétique à 80 à 1 000 MHz CEI 61000-4-3 Le niveau d'essai spécifié est celui A
fréquence radioélectrique de la porteuse, en valeur efficace,
10 V/m
modulé en amplitude avant modulation
80 % MA (1 kHz)
Voir notes 3 et 4
1.3 Décharge kV CEI 61000-4-2 Voir
...