General Information

Abstract

This European Standard specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling.
It also specifies the terms and definitions for the rating and performance of process chillers.
This European Standard does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these.
This European Standard applies to:
-   factory-made units that can be ducted,
-   factory-made liquid chilling packages with integral condensers or for use with remote condensers,
-   factory-made units of either fixed capacity or variable capacity by any means, and
-   air-to-air air conditioners which can also evaporate the condensate on the condenser side.
Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard.
In the case of units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This European Standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement.
The units having their condenser cooled by air and by the evaporation of external additional water should have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, the EN 14511 series applies for the determination of their performance in the heating mode.
NOTE 1   Part load testing of units is dealt with in EN 14825.
NOTE 2   All the symbols given in this text are used regardless of the language.

Status
Withdrawn
Publication Date
13-Mar-2018
Withdrawal Date
22-Sep-2026
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
07-Sep-2022
Completion Date
23-Sep-2026

Buy Documents

Relations

Effective Date
10-Sep-2014
Effective Date
31-Jul-2019
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026
Effective Date
28-Jan-2026

Buy Documents

Get Certified

Connect with accredited certification bodies for this standard

DNV

DNV is an independent assurance and risk management provider.

NA Norway Verified

Lloyd's Register

Lloyd's Register is a global professional services organisation specialising in engineering and technology.

UKAS United Kingdom Verified

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

Sponsored listings

Frequently Asked Questions

EN 14511-1:2018 is a standard published by the European Committee for Standardization (CEN). Its full title is "Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 1: Terms and definitions". This standard covers: This European Standard specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. It also specifies the terms and definitions for the rating and performance of process chillers. This European Standard does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these. This European Standard applies to: - factory-made units that can be ducted, - factory-made liquid chilling packages with integral condensers or for use with remote condensers, - factory-made units of either fixed capacity or variable capacity by any means, and - air-to-air air conditioners which can also evaporate the condensate on the condenser side. Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard. In the case of units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser. This European Standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement. The units having their condenser cooled by air and by the evaporation of external additional water should have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, the EN 14511 series applies for the determination of their performance in the heating mode. NOTE 1 Part load testing of units is dealt with in EN 14825. NOTE 2 All the symbols given in this text are used regardless of the language.

This European Standard specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. It also specifies the terms and definitions for the rating and performance of process chillers. This European Standard does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these. This European Standard applies to: - factory-made units that can be ducted, - factory-made liquid chilling packages with integral condensers or for use with remote condensers, - factory-made units of either fixed capacity or variable capacity by any means, and - air-to-air air conditioners which can also evaporate the condensate on the condenser side. Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard. In the case of units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser. This European Standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement. The units having their condenser cooled by air and by the evaporation of external additional water should have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, the EN 14511 series applies for the determination of their performance in the heating mode. NOTE 1 Part load testing of units is dealt with in EN 14825. NOTE 2 All the symbols given in this text are used regardless of the language.

EN 14511-1:2018 is classified under the following ICS (International Classification for Standards) categories: 01.040.27 - Energy and heat transfer engineering (Vocabularies); 01.040.91 - Construction materials and building (Vocabularies); 27.080 - Heat pumps; 91.140.30 - Ventilation and air-conditioning systems. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 14511-1:2018 has the following relationships with other standards: It is inter standard links to EN 14511-1:2013, EN 14511-1:2022, EN 15502-2-3:2023, EN 14825:2022, EN 16147:2017+A1:2022, EN 14511-3:2018, EN 14511-2:2018, EN 14511-4:2018, EN 13203-6:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 14511-1:2018 is associated with the following European legislation: EU Directives/Regulations: 2009/125/EC, 206/2012; Standardization Mandates: M/488, M/495. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

EN 14511-1:2018 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und -kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 1: BegriffeClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique - Partie 1: Termes et définitionsAir conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 1: Terms and definitions27.080Heat pumps91.140.30VLVWHPLVentilation and air-conditioning systems01.040.23Fluid systems and components for general use (Vocabularies)23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-1:2018SIST EN 14511-1:2018en,fr,de01-maj-2018SIST EN 14511-1:2018SLOVENSKI
STANDARDSIST EN 14511-1:20131DGRPHãþD

EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14511-1
March
t r s z ICS
r sä r v rä t yâ
r sä r v rä { sâ
t yä r z râ
{ sä s v rä u r Supersedes EN
s v w s sæ sã t r s uEnglish Version
Air conditionersá liquid chilling packages and heat pumps for space heating and cooling and process chillersá with electrically driven compressors æ Part
sã Terms and definitions Climatiseursá groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique æ Partie
sã Termes et définitions
Luftkonditioniererá Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und ækühlung und ProzessæKühler mit elektrisch angetriebenen Verdichtern æ Teil
sã Begriffe This European Standard was approved by CEN on
s January
t r s zä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Serbiaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey and United Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Rue de la Science 23,
B-1040 Brussels
t r s z CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s v w s sæ sã t r s z ESIST EN 14511-1:2018

Relationship between this European Standard and the eco-design requirements of Commission Regulation (EU) N° 206/2012 aimed to be covered . 15 Index. 16 Bibliography . 17
IEC Electropedia: available at http://www.electropedia.org/
ISO Online browsing platform: available at http://www.iso.org/obp 3.1 air conditioner device capable of cooling or heating, or both, indoor air, using a vapour compression cycle driven by an electric compressor, including air conditioners that provide additional functionalities such as dehumidification, air purification, ventilation or supplemental air heating by means of electric resistance heating, as well as appliances that may use water (either condensate water that is formed on SIST EN 14511-1:2018

It may have means for heating which can be reversing the refrigerating cycle, such as a heat pump. 3.11 comfort chiller liquid chilling package whose indoor heat exchanger extracts heat from a water-based cooling system designed to operate at leaving chilled water temperatures greater than or equal to 2° C 3.12 process chiller factory-made product integrating at least one compressor and one evaporator, capable of cooling down and continuously maintaining the temperature of a liquid in order to provide cooling to a refrigerated appliance or to a process cooling system Note 1 to entry: It may or may not integrate the condenser, the coolant circuit hardware and other ancillary equipment. 3.13 low temperature process chiller process chiller that is capable of delivering its rated cooling capacity at an indoor heat exchanger outlet temperature of
« t w
¹Cá at standard rating conditions 3.14 medium temperature process chiller process chiller that is capable of delivering its rated cooling capacity at an indoor heat exchanger outlet temperature of
« z
¹Cá at standard rating conditions 3.15 high temperature process chiller process chiller that is capable of delivering its rated cooling capacity at an outlet chilled water temperature of 7 °C 3.16 heat recovery liquid chilling package factory-made liquid chilling package designed for the purpose of chilling liquid and recovering of heat 3.17 heat recovery recovery of heat rejected by the unit whose primary control is in the cooling mode by means of either an additional heat exchanger (e.g. a liquid chiller with an additional condenser) or by transferring the heat through the refrigerating system for use to unit whose primary control remains in the heating mode (e.g. variable refrigerant flow) 3.18 indoor heat exchanger heat exchanger which is designed to transfer heat between the refrigerant and the indoor heat transfer medium Note 1 to entry: In the case of an air conditioner or heat pump operating in the cooling mode, this is the evaporator. In the case of an air conditioner or heat pump operating in the heating mode, this is the condenser. 3.19 outdoor heat exchanger heat exchanger which is designed to transfer heat between any available heat source and the refrigerant SIST EN 14511-1:2018

If heat is removed from the indoor heat exchanger for defrosting, it is taken into account. Note 2 to entry: Expressed in kW. 3.30 heat rejection capacity heat removed by the heat transfer medium of the condenser per unit of time Note 1 to entry:
This applies only to heat recovery liquid chilling packages. Note 2 to entry: Expressed in kW. 3.31 heat recovery capacity heat removed by the heat transfer medium of the heat recovery heat exchanger, per unit of time Note 1 to entry:
This applies only to heat recovery liquid chilling packages. Note 2 to entry: Expressed in kW. 3.32 total power input PT power input of all components of the unit Note 1 to entry: Expressed in kW. 3.33 effective power input PE average electrical power input of the unit w
...